 Νέα > Νέα 2014 > SUMMARY OF F-GAS REGULATIONS- KEY DATES- INFO GRAPHIC

The new F-Gas Regulations will reduce F-Gas emissions by two-thirds of today's levels by 2030 and ban the use of F-Gases in some new equipment where viable climate-friendly alternatives are readily available. The main novelty and driver for moving towards climate-friendly technologies is the introduction of a phase-down measure which from 2015 will limit the total amount of hydrofluorocarbons (HFCs) – the most significant group of F-Gases - sold in the EU and reduce their quantities in steps to one-fifth of today's sales by 2030.

This measure is accompanied by a number of new restrictions on the use and sale of F-Gases in equipment. These ambitious measures will build on and benefit from the successful phase-out of ozone-depleting substances which was achieved in the EU 10 years ahead of the internationally agreed schedule.

Common HFCs affected by the service and maintenance ban are:

TYPE     GWPs

R404A   3922

R422A   3143

R422D   2729

R507    3985

 

Key Dates:

Ban on new equipment placed on the Market

01/01/2015 - HFCs with GWPs of150 or more 

-Applies to domestic refrigerators and freezers

01/01/2020 - HFCs with GWPs of 2500 and over 

- Applies to hermetically sealed commercial refrigerators and freezers

01/01/2020 - HFCs with GWPs of 2500 or more 

- Applies to stationary refrigeration equipment or it’s associated remote plant. Equipment operating below -50 deg C is exempt

01/01/2020 - HFCs with GWPs of 150 or more 

- Appliesto portable air-conditioning appliances i.e. hermetically sealed equipment which is movable between rooms

01/01/2022 - HFCs with GWPs of 150 and over 

- Applies to hermetically sealed commercial refrigerators and freezers

01/01/2022 - HFCs with a GWP of 150 and over 

- Applies to commercial refrigeration central plant with a capacity of 40 kW or more that contain or are dependent upon for their operation, HFCs with GWPs of 150 or more - except where used in the primary refrigerant circuit of cascade systems,where HFCs with a GWP of less than 1500 may be used

01/01/2025 

- Applies to single split air-conditioning with less than 3kg charge of HFCs with GWPs of 750 or more

Service and maintenance bans

01/01/2020 - HFCs with GWPs of 2500 or more 

- Applies to equipment with a charge of 40 tonnes CO2  or above (equivalent to 10.4kg of R404A), although equipment operating at below -50 deg C or military applications are exempt

01/01/2030 - Reclaimed HFCs with GWPs of 2500 or more 

- Used for the maintenance or servicing of existing refrigeration equipment – provided they are labelled appropriately

01/01/2030 -Recycled HFCs with GWPs of 2500 or more 

- Used inthe maintenance or servicing of existing refrigeration equipment - provided they have been recovered from such the equipment. Can only be used by the firm that recovered it or by the firm whose installation it was recovered from.

 

[ΠΗΓΗ:http://www.fridgehub.com/]